InteliDrive Lite - 1.2.1 Global guide
174
Setpoint group
Engine protect 2
Related FW
1.2.1
Range [units]
0 - 3600 [s]
Default value
1 s
Force value
Step
1 s
Comm object
14629
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Five setpoints are dedicated for separately adjustment of the delay for each of binary inputs according to the
Class B protection standard.
Note:
The corresponding BIN protection has to be configured as Running only in LiteEdit.
BIN4 Delay
Setpoint group
Engine protect 2
Related FW
1.2.1
Range [units]
0 - 3600 [s]
Default value
1 s
Force value
Step
1 s
Comm object
14649
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Five setpoints are dedicated for separately adjustment of the delay for each of binary inputs according to the
Class B protection standard.
Note:
The corresponding BIN protection has to be configured as Running only in LiteEdit.
BIN5 Delay
Setpoint group
Engine protect 2
Related FW
1.2.1
Range [units]
0 - 600 [s]
Default value
10 s
Force value
Step
1 s
Comm object
8264
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Max time limit of horn sounding. Set to zero if you want to leave the output HORN open. Horn timeout starts
again from the beginning if a new alarm appears before previous Horn timeout has elapsed.
Horn timeout