![ComAp ID-FLX-Lite-PC Global Manual Download Page 81](http://html1.mh-extra.com/html/comap/id-flx-lite-pc/id-flx-lite-pc_global-manual_2638902081.webp)
InteliDrive Lite - 1.2.1 Global guide
81
Events
specification
Protection
type
Information
on binary
output
available
Description
Wrn RA15 fail
WRN
NO
Warning alarm in case of lost
connection to IGL-RA15 module.
Wrn ECU Alarm
WRN
NO
ECU alarm list is not empty
Low BackupBatt
WRN
NO
RTC backup battery is flat
7.2 HistoryFile
InteliDrive IPC stores a record of each important event into the history file. The history file seats 255 records.
When the history file is full, the oldest records are removed.
Note:
To force history download in LiteEdit (direct, modem or internet) open History window and select History |
Read history command.
7.2.1 RecordStructure
Abbreviation
Historical value
Num
Number of historical event
Reason
Event specification
Date
Date of historical event in format DD/MM/YY
Time
Time of historical event in format HH:MM:SS
RPM
Engine speed
RPM3
Engine speed detected on BI3
UBat
Battery voltage
OilP
InteliDrive IPC Analog input 1 value ( default Oil pressure)
EngT
InteliDrive IPC Analog input 2 value ( default Water temperature)
FLvl
InteliDrive IPC Analog input 3 value ( default Fuel level)
AI4
InteliDrive IPC Analog input 4 value
AI5
InteliDrive IPC Analog input 5 value
AI6
InteliDrive IPC Analog input 6 value
AI7
InteliDrive IPC Analog input 7 value
AI8
InteliDrive IPC Analog input 8 value
AI9
InteliDrive IPC Analog input 9 value
AIM1
Plug-in Analog input 1 value
AIM2
Plug-in Analog input 2 value
AIM3
Plug-in Analog input 3 value
AIM4
Plug-in Analog input 4 value
BIN
Binary inputs InteliDrive IPC