InteliDrive Lite - 1.2.1 Global guide
195
Setpoint visibility
Always
Description
Counter 1 (fix linked to Binary physical input 5) counts pulses (falling edges). The counters function depends
on Counter mode 1 setting and does not depend on BIN5 input configuration. The maximal input frequency is
limited op to 4Hz – i.e. the shortest input pulse is 125ms and gap 125ms (not shorter) to be each edge
counted.
CounterConst 1 is conversion (multiplication) factor between number of counted pulses (edges) and output
Statistic value Total 1. The value stays in memory even if cotroller is switched off. Both can be cleared or
adjusted in LiteEdit like other Statistics values when level 3 password is set.
See range of Statistic value Total 1 in table below.
Note:
The number of controller screen characters is limited – i.e. displays ????? when steps over range.
The counter starts from zero again when maximum is reached.
Input
Analog input
Binary input: Request 2 (optional)
Binary input: R Reg Disable (optional)
Output
Analog output:Speed Request
Setpoints
Regulator
:
Reg Input
Reg Bias
Request
Request 2
Reg Gain
Reg Integral
Engine params
:
MinSpeedLim
MaxSpeedLim
Speed Ramp
Statistics value
Screen
From
To
Over
Total 1
Controller
LiteEdit
0,0
9999999,9
429496729,4
?????????
Continue from 0,0