![ComAp ID-FLX-Lite-PC Global Manual Download Page 157](http://html1.mh-extra.com/html/comap/id-flx-lite-pc/id-flx-lite-pc_global-manual_2638902157.webp)
InteliDrive Lite - 1.2.1 Global guide
157
Setpoint group
Engine protect
Related FW
1.2.1
Range [units]
-10 - +1000 [Bar]
Default value
1 Bar
Force value
Step
0.1 Bar
Comm object
8370
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Shutdown limit level for ANALOG INPUT 1.
Setpoint name depends on setting of AIN1 (maximum length is 14 characters).
AIN1 Sd
Setpoint group
Engine protect
Related FW
1.2.1
Range [units]
0 - 180 [s]
Default value
3 s
Force value
Step
1 s
Comm object
8365
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Delay for ANALOG INPUT 1
Setpoint name depends on setting of AIN1 (maximum length is 14 characters).
Note:
Analog input 1 is usually determined to Oil Pressure measurement and it is resistive type of input
with range 0-2500 Ohm.
AIN1 Del