Setpoint group
Engine protect
Related FW
1.2.1
Range [units]
-100 - +10000 [%]
Default value
20 %
Force value
Step
1 %
Comm object
8381
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Warning limit level for ANALOG INPUT 3
Setpoint name depends on setting of AIN3 (maximum length is 14 characters).
AIN3 Wrn
Setpoint group
Engine protect
Related FW
1.2.1
Range [units]
-100 - +10000 [%]
Default value
10 %
Force value
Step
1 %
Comm object
8382
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Shutdown limit level for ANALOG INPUT 3
Setpoint name depends on setting of AIN3 (maximum length is 14 characters).
AIN3 Sd
Setpoint group
Engine protect
Related FW
1.2.1
Range [units]
0 - 180 [s]
Default value
10 s
Force value
Step
1 s
Comm object
8377
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Delay for ANALOG INPUT 3
Setpoint name depends on setting of AIN3 (maximum length is 14 characters).
Note:
Analog input 3 is usually determined to Fuel Level measurement and it is resistive type of input
with range 0-2500 Ohm.
AIN3 Del