InteliDrive Lite - 1.2.1 Global guide
172
Setpoint group
Engine protect
Related FW
1.2.1
Range [units]
0 - 65535 [h]
Default value
10000 h
Force value
Step
1 h
Comm object
9648
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Counting down when engine is running. Service time alarm appears if reaches zero. By setting the value of
65535h the count down is disabled.
Note:
Set the NextServTime = 65535h to disable count down. The setpoint stays constant, but
Statistics value (visible in LiteEdit) displays #### invalid value.
NextServTime
10.1.13 Group: Engine protect 2
Note:
Following setpoints are available from LiteEdit/InteliMonitor only.
Setpoint group
Engine protect 2
Related FW
1.2.1
Range [units]
0 - 300 [s]
Default value
5 s
Force value
Step
1 s
Comm object
8262
Related applications
Config level
Standard
Setpoint visibility
Always
Description
During the start of the engine, some engine protections have to be blocked (e.g. Oil pressure). The
protections are unblocked after the Protection del time. The time starts after reaching Start RPM.
Eng prot del