InteliDrive Lite - 1.2.1 Global guide
24
Image 4.1 Voltage output sensor - connection
Image 4.2 Current output sensor - connection
Analog input
R1
R2
Curve
0 - 10V
150Ω [1%,0,5W]
100Ω [1%,0,5W]
AI 0-10V.CRV
0 - 30V
680Ω [5%,2W]
100Ω [1%,0,5W]
AI 0-30V.CRV
0 - 65V
1500Ω [5%,3W]
100Ω [1%,0,5W]
AI 0-65V.CRV
4 - 20mA
R = 160Ω [1%,0,5W]
AI 4-20mA.CRV
Table 4.1 Table with recommended values
IMPORTANT: Please note that external resistors disconnection, connection incorrect resistors or
input voltage value during operation may cause an analog input destruction.
Practical example: VDO pressure sensor 0 – 6bar with linear voltage output 0 – 10V
Conversion table
Vout [V]
0
1
2
3
4
5
6
7
8
9
10
P [bar]
0
0,6
1,2
1,8
2,4
3
3,6
4,2
4,8
5,4
6
Modify one of analog input in LiteEdit configuration and load curve AI 0-10V.CRV
Than you can change resolution and measured value name witch is default displayed at V (volts).
For example if you have connected pressure sensor and his output voltage is 5V for pressure 3bar you can
change value ‘V’ in column “Dim:” to ‘Bar’ and by sensor specification adjust all corresponding values in this
column. In this case you can change the value at row 6. from 5 to 3