![ComAp ID-FLX-Lite-PC Global Manual Download Page 54](http://html1.mh-extra.com/html/comap/id-flx-lite-pc/id-flx-lite-pc_global-manual_2638902054.webp)
InteliDrive Lite - 1.2.1 Global guide
54
Name
14 characters ASCII string
Contact type
NC
Normally closed
NO
Normally opened
Alarm type
Warning
Shut down
Alarm active
All the time
Engine running only
5.11.3 Binary inputs list
Not used
Binary input has no function. Use this option when binary input is not connected.
Rem start/stop
Binary input is used for external request for engine run in AUT mode only. The engine is started by rising edge
and stopped by falling edge of the signal.
Functionality of this LBI can be disabled by Basic Settings setpoint Rem Start/Stop.
Emergency stop
If the input is opened, shut down is immediately activated. Input is inverted (normally closed) in default
configuration.
Note:
In case of controller hardware or software fail, safe stop of the engine doesn’t have to be ensured. To
back-up the Emergency stop function it is recommended to connect separate circuit for disconnection of Fuel
solenoid and Starter signals.
Sprinkler
If the input is closed all alarms are disabled except the binary input Emergency stop and "engine overspeed
protection".