InteliDrive Lite - 1.2.1 Global guide
16
4 Installation and wiring
4.4 Terminal diagram and dimension
4.1 Putting it into operation
4.1.1 How to install
To ensure proper function:
Wiring for binary inputs and analog inputs must not be run with power cables.
Analog and binary inputs should use shielded cables, especially when length >3m.
Note:
During the configuration of controller or setpoints changes is required a password to the controller. The
default password from ComAp is “0”.
Grounding
To ensure proper function:
Use cable min. 2,5mm2.
Brass M4x10 screw with star washer securing ring type grounding terminal shall be used.
The negative “-“ terminal of the battery has to be properly grounded.
Switchboard and engine has to be grounded in common spot.
Use cable as short as possible to the grounding point.
Wiring
Tightening torque, allowable wire size and type, for the Field-Wiring Terminals:
Based on terminal type PA256:
Specified tightening torque 0.5Nm (4.4 In-lb) 2EDGK: