InteliDrive Lite - 1.2.1 Global guide
148
Setpoint group
Regulator 2
Related FW
1.2.1
Range [units]
Default value
OFF
Force value
Step
Comm object
11842
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Setpoint is determined for selection of analog input for Speed request in the controller’s MAN mode.
OFF: Speed request selection is done by binary inputs. Default state.
CU: AI1-CU: AI9: Speed request via analog input of the controller only. Binary inputs are ignored.
AIO :1-AIO4: Speed request via analog input of extension module IL-NT-AIO only. Binary inputs are ignored.
Note:
Analog speed request is ignored in AUT mode.
LAI SpdRequest
Setpoint group
Regulator 2
Related FW
1.2.1
Range [units]
-200 - +200 [%]
Default value
10
Force value
Step
0.1 %
Comm object
11846
Related applications
Config level
Standard
Setpoint visibility
Always
Description
This setpoint is giving regulator gain factor. See Hint below.
Reg Gain