4-2
Diagnostic Messages when Booting the Devices
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
4.3
Error Messages when Booting the Devices
PLC ?
Brief Description:
PLC start dialog
Before "Boot 2.9" was displayed on the control panel the buttons "ESC"
and "ENTER" had been simultaneously pressed and kept pressed on the
control panel.
As the functional package "Motion Logic" (drive PLC and technology
functions) has been enabled, the display reads "PLC ?". The automatic
start of a PLC boot project was prevented.
By pressing the arrow buttons (arrow down or arrow up) the display
changes between "
Run PLC
" and "
Stop PLC
".
Stop PLC
Brief Description:
Do not start PLC after booting
Pressing the "ENTER" button on the control panel prevents the start of a
PLC boot project.
Run PLC
Brief Description:
Start PLC after booting
When the "ENTER" button is pressed on the control panel, the drive PLC
and a possibly available boot project are started after the booting process.
No IDN on MMC !
Brief Description:
MMC was not formatted correctly
Cause
Remedy
Content of MMC is incorrect. Parameter (*.pbf) or
retain file (*.rbf) is missing
Switch drive off and plug in MMC with correct content
MMC was not formatted correctly
Switch drive off and plug in appropriate MMC
–
or
–
Switch drive off and format MMC again on PC and plug
it in again