Command Diagnostic Messages
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
C0125 Error when reading encoder data => optional encoder
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the transition check from communication phase
2 to
communication phase 3 (C0100) an error during the reading of the
encoder data from the data memory of the optional encoder was
detected.
Note:
Measuring systems with their own data memory are DSF/HSF
and resolvers, as well as measuring systems with EnDat
interface (Heidenhain company) and HIPERFACE
interface
(Stegmann company).
Cause
Remedy
Measuring system cable defective
Check measuring system cable
Measuring system defective
Replace measuring system
Encoder interface card defective
Replace encoder interface card
C0125 - Attributes
Display:
C0125
Mess. no.:
C0125 (hex)