E2814 Undervoltage in mains
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
Supported by Supply Unit:
HMV01
Note:
This warning only occurs for drive controllers of the HCS03
type!
The crest value of the mains voltage during operation has fallen below the
parameterized threshold value. The threshold value can be individually set
by the user via
P-0-0810, Minimum mains crest value
.
Cause
Remedy
Mains voltage falls under load
Check dimensioning of mains connection, increase feed
wire cross section or use matching transformer, if
necessary
Mains voltage too low at power on
Use matching transformer
See also Functional Description "Power Supply"
E2814 - Attributes
Display:
E2814
Mess. no.:
E2814 (hex)