9-86
Command Diagnostic Messages
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
C1215 Command only possible in
’
bb
’
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
When executing the command for determining the commutation offset
(C1200) with the currentless procedure (see
P-0-0522,Control word for
commutation setting
) the drive was detected not to be ready for
operation ("bb").
Cause:
The drive isn
’
t yet ready for operation ("bb")
- or -
the drive is already in drive enable ("AF")
Remedy:
Bring the drive to the ready for operation status ("bb")
C1215 - Attributes
Display:
C1215
Mess. no.:
C1215 (hex)
C1216 Commutation determination not selected
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the execution of the command for commutation offset
determination (C1200) an error was detected.
Cause:
There wasn
’
t any mode for commutation determination selected.
Remedy:
Set a mode for commutation determination in the
P-0-0522,
Commutation setting control word
parameter.
C1216 - Attributes
Display:
C1216
Mess. no.:
C1216 (hex)