7-72
Error Messages
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
F3147 System error channel 1
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
The operatability of safety monitoring functions is cyclically checked in
normal operation.
A system error occurred in channel 1. The drive is decelerated according
to the setting in
P-0-0119, Best possible deceleration
.
The drive automatically switches to safety related standstill and the output
stage is switched off via two channels.
As soon as the axis has stopped the safety door can be opened.
Cause
Remedy
Cyclic test of monitoring functions of safety
technology channel 1 is faulty
Reset module by switching control voltage on and off.
If error occurs repeatedly, replace firmware and/or
hardware
Note:
Only Rexroth service engineers are allowed to replace optional
modules of the control section.
Only Rexroth service engineers or especially trained users are
allowed to replace the control section. The replacement of the
entire drive controller is described in the Project Planning
Manual for the power section.
F3147 - Attributes
Display:
F3147
Mess. no.:
F3147 (hex)