![Bosch REXROTH IndraDrive Troubleshooting Manual Download Page 239](http://html.mh-extra.com/html/bosch/rexroth-indradrive/rexroth-indradrive_troubleshooting-manual_40580239.webp)
8-14
Warning Diagnostic Messages (Exxxx)
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
8.2
Non-Fatal Safety Technology Warning Diagnostic
Messages (E31xx)
E3100 Error when checking input signals
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
When the safety technology has been activated, this warning only occurs
in normal operation. When a safety related operation is selected, the
cause of the error causes the error
F3130 Error when checking input
signals
or
F3141 Plausibility error of selection
to be triggered.
Cause
Remedy
During dynamization of safety function selection not
all input signals are zero. Cause can be error in
wiring of input signals or short circuit of switch
contacts with positive supply voltage
Remove cause of error in wiring of input signals or
replace switch
There are unequal channel states between
channel 1 and 2. Cause can be error in wiring of
input signals or defective switch
Remove cause of error in wiring of input signals or
replace switch
P-0-3221, Max. tolerance time for different
channel states
incorrectly parameterized
Change parameterization of
P-0-3221, Max. tolerance
time for different channel states
E3100 - Attributes
Display:
E3100
Mess. no.:
E3100 (hex)
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01