8-44
Warning Diagnostic Messages (Exxxx)
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
E2818 Phase failure
Supported by Supply Unit:
HMV01
A single-phase mains failure was detected. Power is not switched off
unless undervoltage occurs in the DC bus (F2026).
Cause
Remedy
Mains circuit breaker defective
Replace mains circuit breaker
Incorrect wiring
Check and correct wiring
E2818 - Attributes
Display:
E2818
Mess. no.:
E2818 (hex)
E2819 Mains failure
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
Supported by Supply Unit:
HMV01
A two-phase or three-phase mains failure was detected. Power is not
switched off unless undervoltage occurs in the DC bus (F2026).
Cause
Remedy
Mains circuit breaker defective
Replace mains circuit breaker
Incorrect wiring
Check and correct wiring
E2819 - Attributes
Display:
E2819
Mess. no.:
E2819 (hex)