9-114
Command Diagnostic Messages
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
C3204 Incorrect input for speed
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the execution of the command
P-0-4033, C3200 Command
Calculate data for asynchronous motor
an error was detected.
Cause
Remedy
There is no useful relation between list element 4
(rated speed) in
P-0-4032, Type plate list
asynchronous motor
and rated frequency, i.e.
number of pole pairs cannot be calculated
Correct list element 4 (rated speed) in
P-0-4032, Type
plate list asynchronous motor
C3204 - Attributes
Display:
C3204
Mess. no.:
C3204 (hex)
C3205 Incorrect input for power factor
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the execution of the command
P-0-4033, C3200 Command
Calculate data for asynchronous motor
an error was detected.
Cause
Remedy
Power factor of motor is outside of useful limits
List element 5 (power factor cos
LQ
P-0-4032, Type
plate list asynchronous motor
has to be between 0.5
and 0.999
C3205 - Attributes
Display:
C3205
Mess. no.:
C3205 (hex)
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01