Rexroth IndraDrive
Command Diagnostic Messages
9-115
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
C3206 Incorrect input for power
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the execution of the command
P-0-4033, C3200 Command
Calculate data for asynchronous motor
an error was detected.
Cause:
There is no useful relation between list element 6 (rated power) in
P-0-4032, Type plate list asynchronous motor
and electric power that
results from the other rated data.
Effective electric power of an asynchronous motor results from
1.5
cos
voltage
rated
current
rated
×
×
×
ϕ
Fig. 9-2:
Effective electric power of an asynchronous motor
Mechanical power output has to be smaller than above value because an
efficiency of less than 1 is assumed. Furthermore a mechanical power
output smaller than 40% of effective electric power is not plausible.
Remedy:
Correct values in
P-0-4032, Type plate list asynchronous motor
and
restart command
P-0-4033, C3200 Command Calculate data for
asynchronous motor
.
C3206 - Attributes
Display:
C3206
Mess. no.:
C3206 (hex)
C3207 Type plate list incomplete
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the execution of the command
P-0-4033, C3200 Command
Calculate data for asynchronous motor
an error was detected.
Cause
Remedy
List length of parameter
P-0-4032, Type plate list
asynchronous motor
is shorter than 6 elements or
at least one element has value "0"
Please check: To calculate motor and controller
parameters from type plate of an asynchronous motor,
value higher than "0" has to be entered in all 6 list
elements of
P-0-4032, Type plate list asynchronous
motor
C3207 - Attributes
Display:
C3207
Mess. no.:
C3207 (hex)