C0303 Absolute encoder offset cannot be saved
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
When executing the command for setting absolute measuring (C0300)
the offset of the encoder zero point with regard to the machine zero point
is determined and stored in the data memory of the encoder. It was
impossible to store the offset correctly.
Cause:
The communication between encoder and drive is disturbed.
Remedy:
•
check encoder cable and repair it, if necessary
- or -
•
replace
encoder
C0303 - Attributes
Display:
C0303
Mess. no.:
C0303 (hex)
C0401 Drive active, switching not allowed
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
Supported by Supply Unit:
HMV01
When switching to communication phase
2 (C0400) an error was
recognized.
Cause
Remedy
Command for switching to parameter mode was
started by means of parameter
P-0-4023, C0400
Communication phase 2 transition
although drive
enable had been activated
Complete command and switch drive enable off, then
command can be started again
C0401 - Attributes
Display:
C0401
Mess. no.:
C0401 (hex)