9-102
Command Diagnostic Messages
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
C2402 Error when saving parameters
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the execution of the
S-0-0293, C2400 Selectively backup
working memory procedure command
an error occurred.
Cause:
It was impossible to address the active, non-volatile memory (internal
flash memory or MMC, if plugged in) without error.
Remedy:
•
Start the
S-0-0293, C2400 Selectively backup working memory
procedure command
again. If the error occurs again, then
•
replace MMC (if plugged in) if necessary, then start the command
again. If the error occurs again,
•
contact the service department.
C2402 - Attributes
Display:
C2402
Mess. no.:
C2402 (hex)