8-22
Warning Diagnostic Messages (Exxxx)
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
E2047 Interpolation velocity = 0
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
In operating states/ operating modes in which the drive-internal position
command value interpolator is active, the preset velocity effective in the
drive is monitored with regard to the value "0"; i.e. the monitor is active in
the following operating modes or operating states:
•
drive-internal
interpolation
•
drive-controlled
positioning
•
positioning block mode
•
Drive
Halt
•
position
spindle
•
drive-controlled
homing
•
automatic control loop setting
•
...
Cause
Remedy
Incorrect velocity is preset (value = "0")
(cf.
S-0-0259, Positioning velocity
,
S-0-0041,
Homing velocity
,
P-0-4007, Positioning block
velocity
[i],
S-0-0222, Spindle positioning speed
,
S-0-0091, Bipolar velocity limit value
)
Check parameterization or cyclic command value of
control unit and set value for preset velocity unequal
zero
Analog input to which preset velocity was assigned
is defective or not connected
Check wiring and function of analog input and, if
necessary, replace cable or control section, or the entire
drive controller
Note:
Only Rexroth service engineers or especially trained users are
allowed to replace the control section. The replacement of the
entire drive controller is described in the Project Planning
Manual for the power section.
E2047 - Attributes
Display:
E2047
Mess. no.:
E2047 (hex)
Operating Modes
Commands