Rexroth IndraDrive
Command Diagnostic Messages
9-19
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
C0104 Config. IDN for MDT not configurable
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the transition check from communication phase
2 to
communication phase 3 (C0100) an error with regard to the telegram
configuration of the master communication was detected.
Cause
Remedy
in the
S-0-0015, Telegram type parameter
the
telegram type 7 (configured telegram) was set
set priority telegram (telegram type = 0..6) in
S-0-0015,
Telegram type parameter
in
S-0-0024, Config. list of the master data
telegram
there were some parameters entered that
are not contained in
S-0-0188, List of configurable
data in the MDT
in
S-0-0024, Config. list of the master data telegram
those parameters have to be entered that are contained
in
S-0-0188, List of configurable data in the MDT
Note:
List parameters are only allowed in the multiplex channel.
C0104 - Attributes
Display:
C0104
Mess. no.:
C0104 (hex)