Rexroth IndraDrive
Error Messages
7-25
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
F8201 Safety command for basic initialization incorrect
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
In the booting phase of the drive a basic initialization is carried out on both
safety technology channels. The initialization sequence on channel 2 is
started via an internal command.
Cause
Remedy
Basic initialization on channel 2 is incorrect or
internal command was aborted with timeout
Carry out load defaults procedure for safety technology
(
S-0-0262, C07_x Load defaults procedure command
with
P-0-4090, Index for C07 Load defaults procedure
= 165) and reset module (switch control voltage off and
on again).
Note:
If necessary, repeat procedure if
P-0-3207, Safety
technology password level
is unequal 1.
Incompatible firmware releases on channel 1 and
channel 2
Establish compatible firmware releases on channel 1
and channel 2
If the error occurs repeatedly, the hardware has to be replaced.
Note:
Only Rexroth service engineers or especially trained users are
allowed to replace the control section or the safety technology
module. The replacement of the entire drive controller is
described in the Project Planning Manual for the power
section.
F8201 - Attributes
Display:
F8201
Mess. no.:
F8201 (hex)