7-122
Error Messages
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
F2818 Phase failure
Supported by Supply Unit:
HMV01
A single-phase mains failure of more than 2 seconds was detected. The
device was switched off.
Cause
Remedy
Mains circuit breaker defective
Replace mains circuit breaker
Incorrect wiring
Check and correct wiring
F2818 - Attributes
Display:
F2818
Mess. no.:
F2818 (hex)
F2819 Mains failure
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
Supported by Supply Unit:
HMV01
The mains has failed. The DC bus voltage has fallen below a threshold
value so that a new soft start process is required.
Cause
Remedy
Mains failure (permanent or temporary)
Search and remove cause of mains failure
See also Functional Description "Power Supply"
F2819 - Attributes
Display:
F2819
Mess. no.:
F2819 (hex)