Rexroth IndraDrive
Command Diagnostic Messages
9-119
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
C3506 Correction value table cannot be stored
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the execution of the command
P-0-0340, C3500 Command
Determine encoder correction values
an error was detected.
Cause
Remedy
Determined correction value table (
P-0-0342,
Correction value table for encoder correction
) is
incomplete
Execute command
P-0-0340, C3500 Command
Determine encoder correction values
again, select
different acquisition velocity
Due to hardware problem, determined correction
value table (
P-0-0342, Correction value table for
encoder correction
) cannot be stored in drive
Replace device
C3506 - Attributes
Display:
C3506
Mess. no.:
C3506 (hex)
C3701 Error when manually unlocking the safety door
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
The command
C3700 Manually unlocking the safety door
was not or
incorrectly executed.
Cause
Remedy
Drive still is in normal operation, there hasn
’
t been
any safety function activated yet
Clear command
C3700 Manually unlocking the safety
door
. Select safety function via operating mode switch
Error in command processing (time exceeded)
Switch control voltage of controller off and on. Execute
command
C3700 Manually unlocking the safety door
again. If error is displayed again: replace controller
Command was started with safety function being
active, but requirements for command execution are
missing
Clear command
C3700 Manually unlocking the safety
door
C3701 - Attributes
Display:
C3701
Mess. no.:
C3701 (hex)