Rexroth IndraDrive
Command Diagnostic Messages
9-67
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
C0260 Incremental enc. emulator resol. cannot be displayed
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
In the case of incremental encoder emulation, inadmissible overflow can
occur for increment output. In order to avoid this overflow,
P-0-0903,
Encoder emulation resolution
has to be parameterized accordingly.
In the case of modulo processing, the overflow takes place at the modulo
value entered in
S-0-0103, Modulo value
:
29
2
0103
0
S
0079
0
S
0903
0
P
×
−
−
−
−
=
−
−
S-0-0103:
S-0-0103, Modulo value
P-0-0903:
P-0-0903, Encoder emulation resolution
S-0-0079:
S-0-0079, Rotational position resolution
Otherwise the overflow takes place at the value entered in
S-0-0278,
Maximum travel range
:
29
2
0278
0
S
0079
0
S
0903
0
P
×
−
−
−
−
=
−
−
P-0-0903:
P-0-0903, Encoder emulation resolution
S-0-0079:
S-0-0079, Rotational position resolution
S-0-0278
S-0-0278, Maximum travel range
Cause
Remedy
Resolution of emulated signal is not correct for
modulo range / travel range
Reduce resolution entered in
P-0-0903, Encoder
emulation resolution
- or -
Reduce
S-0-0278, Maximum travel range
See also Functional Description "Incremental Encoder Emulation"