3.8 History
Log
The system stores 254 events from all areas in its
event log.
All events can be stored even if the control panel
does not send a report for them. You can view the log
at a text keypad, print it locally using an RS-232 Serial
Interface Module (DX4010i or DX4010) and a serial
printer, or upload it to the Remote Programming
Software (RPS).
See Control Panel Events and Reporting Formats on
page 124 for a listing of log events. For information on
viewing and understanding the log events, see History
Log on page 123. For more information on the log
threshold, see Log Supervision Configuration on page
50.
3.9
Wireless (RF) Devices
The control panel can support a variety of wireless
sensor devices, which can be included in the 40-zone
maximum (24-zone maximum on the DS7220V2).
4.0 Control
Panel
Assembly
The control panel is pre-assembled from the factory in
the CX1011 enclosure. You should receive the
following parts:
Literature Pack
•
Installer’s Guide (this document) (P/N: 4998152533)
•
System Worksheet (P/N: 4998152532)
•
Release Notes (P/N: 4998152534)
•
User’s Guide (P/N : 4998152530)
Assembly
•
Red Battery Lead (P/N: 47720B)
•
Black Battery Lead (P/N: 47721B)
•
2.2 k EOL Resistor Pack (P/N: 47819); 2 packs, 8
EOLs in each pack
•
Spare Fuse (P/N: 4998122444B)
5.0
Listings and Approvals
•
•
This product fulfills the requirements of
EN 50131-1, 50131-2, CLC/TS 50131-3
6.0 System
Options
6.1 Arming
Devices
•
DS7445i LED Keypad: LED keypad that displays
up to 16 zones.
•
DS7445V2 LED Keypad: LED keypad in new
faceplate design.
•
DS7447E Text Keypad: Text keypad that displays
system information and programmable text.
•
DS7447V2 Text Keypad: Text keypad in new
faceplate design.
•
Door Access Control Module (DACM): The
DACM grants or restricts access to a door using a
keypad/credential reader, a Request to Exit (REX)
input, or a door contact. Each DACM supervises
one door.
6.2
Data Bus Devices
•
DX2010 Input Expander: Provides 8 additional
input loops. The DS7240V2 supports up to 5
modules; the DS7220V2 supports up to 3 modules.
Also available: DX2013 (DX2010 mounted on
angle bracket); DX2014 (DX2010 with AE20 ABS
plastic enclosure).
•
DX3010 Octo-Output Expander: Provides 8
independent, programmable Form “C” relay outputs.
The DS7240V2 supports up to 2 modules; the
DS7220V2 supports 1 module. Also available:
DX3013 (DX3010 mounted on angle bracket).
•
DX4010i RS-232 Serial Interface Module: DTE
RS-232 serial interface module that provides a
connection point to the system for serial devices
such as a printer. Can also be used to create a
remote programming direct connection with RPS. It
does not occupy a control panel address when used
this way. One allowed per system.
•
DX4010 RS-232 Serial Interface Module: Provides
a connection point to the system for serial devices
such as a printer. Can also be used to create a
remote programming direct connection with RPS.
Does not occupy a control panel address when
used this way. One allowed per system.
•
DX4020 Network Interface Module: Provides bi-
directional communication over an Ethernet
network. Can also be used for remote programming
sessions with RPS. One allowed per system.
Firmware revision 2.10 or greater is required to use
the DX4020.