DS7200V2-UK Installer's Guide
Copyright
2007 Bosch Security Systems, Inc.
P/N: 4998152533-02 Page 133
PART V: REFERENCE MATERIALS
Event #
Event as shown
in Panel Log
SIA Report
SIA Report Data
Contact ID Report
Event Description
Zone Types
Linked to Event
RPS
Event
Group
Status
Reports
175 Rstrl,Alarm,Miss Local
Event
Only
Local Event Only
Restoral from Missing,
Non-Fire zones. Local
event, no report sent.
Any non-fire
zone type
8
176 Rstrl,Fault,Miss Local
Event
Only
Local Event Only
Restoral from Fault
(Trouble), Non-Fire
zones. Local event, no
report.
Any non-fire
zone type
8
177
Rstl,Low Signl
Local Event
Only
Local Event Only
Restoral from Alternate
Communication Low
Signal Strength event.
12
R
S
178 UnBypss,Fire,
RPS Fire
Unbypass
ri {area (?)} FU {loop}
571 Fire bypass
Bypass on Fire zone
type cleared using
RPS (un-bypass)
1- Fire
2- Fire with
Alarm
Verification
179 UnBypss,Ctrl,
RPS
Burglary
Unbypass
ri {area (?)} BU {loop} 570 Zone/Sensor
bypass
Bypass on zone type
cleared using RPS
(un-bypass)
10 to 15- Zone
Types
180 UnBypss,24hr,
RPS
Burglary
Unbypass
ri {area (?)} BU {loop} 572 24 hour zone
bypass
Bypass on 24-hour
zone type cleared
using RPS (un-bypass)
3 to 9- 24-hour,
Non-Fire Zone
Types
181*
RF Battery Low
Transmitter
Battery
Trouble
ri {0} XT {user}
384 RF Low Battery Low battery condition
on RF Keyfob.
9
R
182*
RF Battery Rstl
Transmitter
Battery
Restoral
ri {0} XR {user}
384 RF Low Battery Low battery condition
on RF Keyfob
restored.
9
R
183 Default
PINS
Local
Event
Only
Local Event Only
Installer or User PINS
have not been
changed from default.
184
Default PINS Rstl
Local Event
Only
Local Event Only
Installer or User
default PINS have
been changed.
185
Bad Set
Exit Error
Ri {area} EE {user}
454 Failed to Close Bad Set condition.
3
186
Confirmed Alarm
Burglary
B V {area}
139 Intrusion
Confirmed Alarm.
3
187
Dbus Missng Alrm Tamper
Alarm
TA 0041
137 Tamper Alarm
Data bus device not
responding to polling.
12
R
S
188
Dbs Mis Alm Rstl
Tamper
Restoral
TR 0041
137 Tamper Alarm
Data bus device
declared as missing
now responding to
polling.
12
R
S
189
Dbus Tamper Alrm Tamper
Alarm
TA 0042
137 Tamper Alarm
Tamper open on Data
bus Device Tamper.
12
R
S
190
Dbs Tmp Alm Rstl Tamper
Restoral
TR 0042
137 Tamper Alarm
Data bus device
tamper restoral.
12
R
S
191
Dbus Trouble Alm Tamper
Alarm
TA 0043
137 Tamper Alarm
Trouble detected on
data bus device.
12
R
S
192
Dbs Trb Alm Rstl
Tamper
Restoral
TR 0043
137 Tamper Alarm
Data bus device
trouble condition
cleared.
12
R
S
193
Siren Missg Alrm
Tamper
Alarm
TA 0044
137 Tamper Alarm
Trouble condition
detected on PO 2
configured as
supervised siren
output.
12
R
S
194
Siren Alarm Rstl
Tamper
Restoral
TR 0044
137 Tamper Alarm
Trouble condition on
supervised siren
output cleared.
12
R
S
Table 47: Control Panel Events and Reporting Formats (continued)