Page 22 P/N: 4998152533-02
Copyright
2007 Bosch Security Systems, Inc.
DS7200V2-UK Installer's Guide
PART II: SYSTEM INSTALLATION AND SETUP
Set the address DIP switches as shown in Table 8.
Shaded cells only apply to the DS7240V2.
DX2010 DIP Switch Settings
DIP
Switches
S1
S2
S3
S4
S5
S6
Data Bus
Address
32
16
8
4
2
1
101
OFF OFF OFF OFF OFF OFF
102
OFF OFF OFF OFF OFF ON
103
OFF OFF OFF OFF ON OFF
104
OFF
OFF
OFF
OFF
ON
ON
105
OFF
OFF
OFF
ON
OFF
OFF
106 OFF
OFF
OFF
ON OFF ON
107
OFF
OFF
OFF
ON
ON
OFF
Table 8: DX2010 DIP Switch Settings
See Figure 27 for proper DX2010 DIP switch
configuration.
ON
1
2
3
4
5
6
OFF
ON
Example:
Module Address 102
Figure 27: DX2010 DIP Switch Configuration
18.8 DX2010
Status
LED
•
One flash per second indicates normal operation.
•
LED steady ON can indicate any of the following:
−
“G” wire is not connected or there is a
communications problem between the control
panel and the DX2010.
−
No locations (zones) are assigned to the DX2010
with this address. See Locations on page 72 for
details.
−
DX2010 address is not set correctly.
•
LED OFF indicates that there is no power to the
module.
ON
1
2
3
4
5
6
Status LED
DIP switches
Figure 28: DX2010 Status LED Location
18.9 DX2010
Supervision
The control panel supervises proper communication
to the DX2010. If it fails to communicate with the
DX2010, it sends a “Dbus Missing” {125} report.
19.0 Off-board Outputs (DX3010)
19.1 Overview
The DX3010 Output Expander allows you to add
outputs to your system in groups of eight.
The DS7240V2 supports up to 20 programmable
outputs (4 on-board, 16 off-board via 2 DX3010
Output Expanders).
The DS7220V2 supports up to 12 programmable
utputs (4 on-board, 8 off-board via 1 DX3010
Output Expander).
You can assign any of the programmable output
functions to the DX3010’s individual outputs
separately. See Outputs on page 86 for
programming details.
•
DX3013 Output Expander: An Octo-Output
Expander mounted on an angle bracket for
installation inside the CX1011 Enclosure.
•
Current Draw: 10 mA Standby plus 40 mA for
each energized output (relay) for a total of 330 mA
maximum with all eight outputs energized.
Refer to the DX3010 Installation Guide (P/N: 49529)
for complete installation, addressing and operating
instructions.
19.2 DX3010
Configuration
Outputs might activate when setting the
DX3010’s address DIP switches,
programming the control panel, resetting
the control panel, or applying power to the
control panel. Disconnect equipment
connected to outputs when performing
these functions.
The DX3010 relay outputs are not
supervised and cannot be used in fire or
combined fire/burglary installations for
primary indicating devices.
19.3 DX3010
Relay
Outputs
Each DX3010 output provides a Form “C” dry contact
rated for 5.0 A at 28 VDC. Normally Open, Common,
and Normally Closed terminals are available for each
relay output. When an individual output is activated,
there is continuity between the Normally Open and
Common terminals. When the output is not activated,
there is continuity between the Normally Closed and
Common terminals.