DS7200V2-UK Installer's Guide
Copyright
2007 Bosch Security Systems, Inc.
P/N: 4998152533-02 Page 131
PART V: REFERENCE MATERIALS
Event #
Event as shown
in Panel Log
SIA Report
SIA Report Data
Contact ID Report
Event Description
Zone Types
Linked to Event
RPS
Event
Group
Status
Reports
139 Tamper,
Fault
Tamper
Trouble
ri {area} TT {loop}
380 Sensor Trouble Fault (Trouble)
condition on Tamper or
Voice Active zone
types.
4-Tamper 6
140 Emergency,
Fault Emergency
Trouble
ri {area} QT {loop}
380 Sensor Trouble Fault (Trouble)
condition on
Emergency zone type.
5- Emergency
6
141 Panic,
Fault
Panic
Trouble
ri {area} PT {loop}
375 Panic Zone
Trouble
Fault (Trouble)
condition on Panic
zone type.
6- Visible Panic
6
142 Invisible,
Fault
Holdup
Trouble
ri {area} HT {loop}
375 Panic Zone
Trouble
Fault (Trouble)
condition on Invisible
zone type.
7-Invisible Panic
6
143
24-hr Burg, Fault
Burglary
Trouble
ri {area} BT {loop}
380 Sensor Trouble Fault (Trouble)
condition on Burglary
zone type.
8- Burglary
15- Door
6
144 Cntrl,Dly,
Fault
Burglary
Trouble
ri {area} BT {loop}
380 Sensor Trouble Fault (Trouble)
condition on Delay
zone types.
11- Delay 1
12- Delay 2
6
145 Cntrl,
Fault
Burglary
Trouble
ri {area} BT {loop}
380 Sensor Trouble Fault (Trouble)
condition on
Keyswitch, Follower,
and Instant zone
types.
10- Keyswitch
13- Follower
14- Instant
6
146 Rstrl,Flt,Tmpr
Tamper
Trouble
Restore
ri {area} TJ
380 Sensor Trouble Restoral from fault
(trouble) condition on
Tamper or Voice
Active zone types.
4-Tamper 8
147 Rstrl,Flt,Emerg
Emergency
Trouble
Restore
ri {area} QJ {loop}
380 Sensor Trouble Restoral from fault
(trouble) condition on
Emergency zone type.
5- Emergency
8
148 Rstrl,Flt,Panic
Panic
Trouble
Restore
ri {area} PJ {loop}
375 Panic Zone
Trouble
Restoral from fault
(trouble) condition on
Panic zone type.
6- Visible Panic
8
149 Rstrl,Flt,Invis
Holdup
Trouble
Restore
ri {area} HJ {loop}
375 Panic Zone
Trouble
Restoral from fault
(trouble) condition on
Invisible zone type.
7-Invisible Panic
8
150 Rstrl,Flt,24-hr
Burglary
Trouble
Restore
ri {area} BJ {loop}
380 Sensor Trouble Restoral from fault
(trouble) condition on
Burglary zone type.
8- Burglary
15- Door
8
151 Rstrl,Flt,Dly
Burglary
Trouble
Restore
ri {area} BJ {loop}
380 Sensor Trouble Restoral from fault
(trouble) condition on
Delay zone types.
11- Delay 1
12- Delay 2
8
152 Rstrl,Flt,Cntrl
Burglary
Trouble
Restore
ri {area} BJ {loop}
380 Sensor Trouble Restoral from fault
(trouble) condition on
Keyswitch, Follower,
and Instant zone
types.
10- Keyswitch
13- Follower
14- Instant
8
153
User Code Area
Set
User Code
Added
id {user doing change}
JY {changed user}
User Code ‘added’ by
assigning area.
16
R
154
User Code Change User Code
Changed
id {user doing change}
JV {changed user}
User Code changed.
16
R
155
User Code Delete User Code
Deleted
id {user doing change}
JX {changed user}
User Code deleted.
16
R
Table 47: Control Panel Events and Reporting Formats (continued)