DS7200V2-UK Installer's Guide
Copyright
2007 Bosch Security Systems, Inc.
P/N: 4998152533-02 Page 27
PART II: SYSTEM INSTALLATION AND SETUP
−
DX4010: Wire the flying leads of the colored
cable connector (included with control panel –
P/N: 15-04298-000) to the DX4010’s data bus
terminals. See Figure 40.
Com Port
DX4010
Null Modem Cable
Control Panel
AUX/Data
Connector Pin
Location
DX4010 Data Bus
Red
Yellow
Green
Black (GND)
BATT+
BATT-
Serial Port
Figure 40: DX4010 Direct Connection
No additional control panel/module (DX4010i or
DX4010) programming is required for on-site
programming using when using a direct connection.
20.4
DX4010i/DX4010 Configuration Jumpers
The jumpers are located in different positions
on the DX4010i and DX4010 PCB’s. However,
they function the same. The figures in this
section show the DX4010i’s PCB.
20.4.1 P1 – DB9 Cable Ground Enable
Some devices connected to the DB9 connector can
cause a ground fault condition on the control panel. If
this occurs, removing the plug across the P1 jumper
pins can clear the ground condition.
Some devices can cause a ground fault even if the P1
jumper plug is removed.
DB9 GND
ENABLE
P1
DB9 Ground
Enable Pins (P1)
Disabled
Enabled
Figure 41: P1 Jumper Pin Settings
20.4.2 P2 –LED Enable
Use the diagnostic LEDs for troubleshooting
purposes. See Figure 42 to enable/disable these
LEDs.
SER
Rx
Tx
BUS
Rx Tx
LED
ENABLE
P6
P2
LED Enable Pins (P2)
Diagnostic LEDs
Disabled
Enabled
Figure 42: P2 Jumper Pin Settings
Diagnostic LED
Function
BUS RX LED
Data Bus receive data from control
panel.
BUS TX LED
Data Bus transmit data to control panel.
SER RX LED
RS-232 receive data from serial device.
SER TX LED
RS-232 transmit data from serial
device.
Table 13: DX4010i/DX4010 Diagnostic LED Functions
20.5 DX4010i/DX4010
Addressing
Set the DIP Switch address to 250 when using the
module as a serial device interface. The DX4010
does not use DIP Switches 7 and 8.
ON
1
2
3
4
5
6
7
8
OFF
ON
Address 250 Settings
Figure 43: RS-232 Device DIP Switch Setting
20.6 DX4010i/DX4010
Supervision
The control panel supervises proper communication
to the module when it is not used for a RPS direct
connection. If it fails to communicate with the module,
it sends a “Dbus Missing” {125} report.