DS7200V2-UK Installer's Guide
Copyright
2007 Bosch Security Systems, Inc.
P/N: 4998152533-02 Page 129
PART V: REFERENCE MATERIALS
Event #
Event as shown
in Panel Log
SIA Report
SIA Report Data
Contact ID Report
Event Description
Zone Types
Linked to
Event
RPS
Event
Group
Status
Reports
94 Open,RPS,Alarm Disarm
from
Alarm
ri {area} OR {254}
400 Open/Close
Opening after Alarm event
by RPS.
95 Open,Usr,Alarm Disarm
from
Alarm
ri {area} OR {user}
401 O/C by User
Opening after Alarm event,
ID reported.
10
96 Open,KS,Alarm Disarm
from
Alarm
ri {area} OR {255}
409 Keyswitch O/C Opening after Alarm event
by Keyswitch
10
97 Reserved
98 Params
Changed
Parameter
Changed
YG 306
Panel
Programming
Changed
Panel Parameters Changed 12
R
99
Phone Line Fail
Phone Line
Trouble
LT {phone line}
351 Telco 1 fault
Phone line voltage less than
3 volts for 40 seconds.
12
R
S
100
Phone Line Rstl
Phone Line
Restoral
LR {phone line}
351 Telco 1 fault
After Phone Line Fail event,
phone line voltage detected
at greater than 3 volts for 40
seconds.
12
R
S
101
Bad Call to RPS
Remote
Programmer
Call Failed
RA 413
Unsuccessful
access
Panel attempted call to
RPS, but was unsuccessful.
12
R
102
RPS Access Fail
Remote
Program
Fail
RU 413
Unsuccessful
access
RPS attempted to connect
to panel but was not
successful.
R
103
RPS Access OK
Valid
Remote
Access
RS 412
Successful
Download/Access
RPS successfully
connected to and
disconnected from panel.
R
104
Re-Boot,Panel
Power Up
RR
305 System reset
Normal start up or reset by
RPS.
R
S
105
Re-Boot,DBus
Power Up
pi {SDI address} RR
339 Exp. Module
Reset
Unexpected reset (reboot)
from Option Bus device.
12
R
S
106 Output
Reset,Usr Relay
Open id {user} RO {output #} 320 Sounder/Relay Output Reset by User
16
R
107 Output
Reset,Tmr Relay
Open id {252} RO {output #} 320 Sounder/Relay Output Reset by Sked
(Timer)
16
R
108 Output
Reset,
RPS
Relay Open id {254} RO {output #} 320 Sounder/Relay Output Reset by RPS
R
109 Output
Set,Usr
Relay
Close id {user} RC {output #} 320 Sounder/Relay Output Set by User
16
R
110 Output
Set,Tmr Relay
Close id {252} RC {output #} 320 Sounder/Relay Output Set by Sked (Timer)
16
R
111 Output
Set,RPS Relay
Close id {254} RC {output #} 320 Sounder/Relay Output Set by RPS
R
112 Rstrl,Tamper
Tamper
Restoral
ri {area} TR {loop}
137 Tamper
Restoral from alarm,
Tamper zone type.
4- Tamper
8
113 Rstrl,Emergency Emergency
Restoral
ri {area} QR {loop}
101 Personal
Emergency
Restoral from alarm,
Emergency zone type.
5-
Emergency
8
114 Rstrl,Panic
Panic
Restoral
ri {area} PR {loop}
120 Panic
Restoral from alarm, Panic
zone type.
6- Visible
Panic
8
115 Rstrl,Invisible
Holdup
Restoral
ri {area} HR {loop}
120 Panic
Restoral from alarm,
Invisible zone type.
7-Invisible
Panic
8
116 Rstrl,24-hr
Burg Burglary
Restoral
ri {area} BR {loop}
133 24hr (Safe)
Restoral from alarm, 24-
hour burglary zone types.
8- Burglary
15- Door
8
117 Rstrl,Cntrl,Dly
Burglary
Restoral
ri {area} BR {loop}
134 Entry/Exit
Restoral from alarm, zone
types.
11- Delay 1
12- Delay 2
8
118 Rstrl,Cntrl
Burglary
Restoral
ri {area} BR {loop}
130 Burglary
Restoral from alarm, zone
types.
10-
Keyswitch
13- Follower
14- Instant
8
119 Rcvr
Jam
RF
Interference
XQ {RF device #}
344 RF Receiver
Jam Detect
Jammed condition detected
on premises RF receiver.
9
R
S
120
Rcvr Jam Rstl
RF
Interference
Restoral
XH {RF device #}
344 RF Receiver
Jam Detect
Restoral
Jammed condition detected
on premises RF receiver
cleared.
9
R
S
Table 47: Control Panel Events and Reporting Formats (continued)