PART IV: CONTROL PANEL PROGRAMMING
57.0 DACM
Configuration
The control panel supports up to 8 DACMs. However, each DACM added to the system replaces one keypad. If 8
DACMs are added, you cannot add a keypad. For full system control, make sure at least one text keypad is
included in the system.
For complete installation, programming, addressing, and operation instructions, see the documentation
supplied with the DACM.
Configuring a DACM into the control panel is a three-step process:
1. Using
Table 27: Location Configuration Parameters
on page 72, assign the DACM’s door contact as a location. For
example, DACM #1’s door contact will be assigned to Location #5.
a. Enter “6” at Address 0726 for the device type.
b. Assign a zone function and enter it in Address 0727.
c.
Assign an area to the DACM in Address 0728. Each DACM’s door contact can only use one location.
d. Repeat the area assignment in Keypad #/Door Access Control Module (DACM) Area Options . For example,
if you selected Area 1 for Address 0728, then you must enter “9” in Address 0679. This address is for
Keypad/DACM #1. “9” identifies the device as a DACM #1 in Area 1.
e. Assign a zone number in Addresses 0729-0730 if the zone number must be different than the location
number.
2. Enter the location number in DACM Location Assignment . For this example, enter “0” in Address 3546, and “5” in
Address 03547. This assigns the control panel’s Location #5 to DACM #1.
3. Assign global options in Address 3562 (see DACM Global Options on page 117). The entry you make here affects all
DACMs connected to the control panel.
Keypad #/Door Access Control Module (DACM) Area Options
•
Address:
−
Keypad/DACM 1: 0679
−
Keypad/DACM 2: 0681
−
Keypad/DACM 3: 0683
−
Keypad/DACM 4: 0685
−
Keypad/DACM 5: 0687
−
Keypad/DACM 6: 0689
−
Keypad/DACM 7: 0691
−
Keypad/DACM 8: 0693
•
Default:
−
Keypad 1/DACM: 1 (Device is a keypad/DACM assigned to Area 1)
−
Keypad/DACM 2-8: 0 (No keypad/DACM assigned - disabled)
•
Selections: 0-4, 9-12
Enter This Data Digit to Select Options
Keypad/DACM Area Options
0
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15
Keypad/DACM not assigned (disabled)
•
Assign Keypad/DACM to Area 1
•
•
Assign Keypad/DACM to Area 2
•
•
Assign Keypad/DACM to Area 3 (DS7240V2 only)
•
•
Assign Keypad/DACM to Area 4 (DS7240V2 only)
•
•
Device is a Keypad
•
•
•
•
Device is a DACM
•
•
•
•
This parameter identifies the device connected to the control panel’s Data Bus (Addresses 1 to 8) as a DACM, and assigns the
DACM to an area.
The control panel supervises the connection to the DACM. If it fails to communicate with the control panel, the control panel
sends a “DBus Missing” {125} report.