PART IV: CONTROL PANEL PROGRAMMING
Digit
1
Digit
2
Function Type
Description
1 0
PO 2 (on-board) Siren
Supervision Fail
Output activates when a Siren Supervision Fail condition is detected. For Steady or Pulse modes, the
output remains activated until the condition is cleared and the [System Reset] key is pressed.
1 1
Sensor
Trouble
Monitor
Output activates when a Sensor Trouble Monitor condition is detected in conjunction with the selection
made for the Sensor Monitor Time setting. For Steady or Pulse modes, the output remains activated
until the Sensor Monitor Trouble condition is cleared.
1 2
Duress, [#][4][7] (reset)
resets.
Output activates whenever a Duress PIN is entered. For Steady or Pulse modes, the output remains
activated until user presses [System Reset].
1 3
User Tamper, [#][4][7]
(reset) resets.
Output activates on a User Tamper event. For Steady or Pulse modes, the output remains activated
until user presses [System Reset].
1 4
Arming Beeps (for
keyswitch/RF arming)
Disarm/All On/Perimeter Only/Partial On Beeps for keyswitch/RF arming. 1=Off, 2=All, 3=Perimeter
Only. Mode and Time parameters do not apply.
This function works in conjunction with Address
1039. See
Global Output Options
on page 84. Available for on-board outputs only
.
1 5
Bell Time – Starts on
any Alarm Event. PIN
entry Stops. Activates
on Bell Test.
Output activates on any alarm event. Entering PIN terminates Bell Time. For Steady and Pulse modes,
the output remains activated for the duration programmed in the Bell Time parameter.
1
6
Strobe
PIN entry resets the function.
1 7
Silent
Alarm
Activated by alarm on non-fire zones programmed for No Alarm Output. Follows Bell Time for Steady
and Pulse modes. PIN stops. The following conditions activate Silent Alarm:
-
Help Function Key programmed for Fire or Emergency and no Alarm Output
-
RF Keyfob programmed for Fire or Emergency and no Alarm Output
-
A zone programmed for Fire or Fire with Verify and no Alarm Output
-
Any zone not programmed for Invisible Panic that is programmed for no Alarm Output
-
Any armed zone programmed as a controlled type that goes from Supervised to Missing and
programmed for no Alarm Output
-
Any armed keyswitch programmed for no Alarm Output that goes from Supervised to Missing or
Short to Missing
-
Any zone programmed for Swinger Count and Swinger Count for Alarm Output that reaches its
programmed value
1 8
Alarm – All On,
Perimeter Only, and
Partial On Arming, Non-
fire 24 hour alarms
Activated by alarm on zone when All On, Perimeter Only, and Partial On Armed, or by alarm on Non-
fire 24 hour zone, and by user/installer ‘Bell Test’. Follows Bell Time for Steady and Pulse modes. PIN
resets.
Follows programming for ‘Alarm’ output types.
1 9
Alarm – Perimeter Only
and Partial On Arming
Modes, Non-fire 24 hour
alarms
Activated by alarm on zone when Perimeter Only, and Partial On Armed, or by alarm on Non-fire 24
hour zone, and by user/installer ‘Bell Test’. Follows bell time for Steady and Pulse modes. PIN resets.
Follows programming ‘Alarm’ output types
.
1 10
Alarm –Controlled
zones, 24-hr zones (Fire
and Non-Fire)
Activated by alarm on zone when All On, Perimeter Only, and Partial On Armed, or by alarm on Fire
and Non-fire 24 hour zone, and by user/installer ‘Bell Test’. Follows bell time for Steady and Pulse
modes. Pulses in Temporal Code 3 format for Fire alarms only. PIN resets.
Off-board outputs cannot provide output in Temporal Code 3 format (only on-board outputs).
Off-board outputs provide a steady output. Follows programming for ‘Alarm’ output types.
Temporal Code 3 for Fire alarms only
.
1 11
Fire
Alarm
Activated by alarm on Fire zone, and by user/installer ‘Bell Test’. Follows Bell Time. Pulses in Temporal
Code 3 format. Mode and Time parameters do not apply. PIN resets.
Off-board outputs cannot provide output in Temporal Code 3 format (only on-board outputs).
Off-board outputs provide a steady output. Follows programming for ‘Alarm’ output types.
1
12
Fire Alarm, Latching
Activated by alarm on Fire zone, and by user/installer ‘Bell Test’. Does not pulse in Temporal Code 3
format. Mode and Time parameters do not apply. [#][4][7] resets.
Follows programming for ‘Alarm’
output types.
1 13
Fire
Verification/Reset
Inverted, resettable output used with Fire Verification zones. Verification for Fire Verification Zone
Function type and [System Reset] activate output for approximately 15 seconds. Mode and Time
parameters do not apply. Used for 4-wire smoke detectors.
1
14
System Trouble
Activates on any System Trouble. Resets when all system troubles are clear.
1 15
[O] Key (Trapezoid Key
on RF Key Fob)
Activates when Trapezoid Key on RF Keyfob is pressed. [System Reset] resets. Pressing O (trapezoid)
key again also resets output when Output Mode is set to Toggle. This output type is event-driven. See
Mode (Steady, Pulse, One Shot), Output ## on page 92 for more information.
2 0
[P] Key (Rising Sun Key
on RF Fob)
Activates when Rising Sun Key on RF Keyfob is pressed. [System Reset] resets. Pressing P (sun) key
again also resets output when Output Mode is set to Toggle. This output type is event-driven. See
Mode (Steady, Pulse, One Shot), Output ## on page 92 for more information.
2
1
‘Panic’ on RF Fob
Activates when Arm Key (locked icon) and Disarm Key (unlocked icon) on RF Keyfob are pressed at
the same time, or when the [Q] button is pressed and it is set to Duress. See “[Q] Button Alarm
Response Options” in the DS7200V2 Expert Programming Guide (P/N: 4998153891). [#][4][7] resets.
Table 32: Output Function Types (continued)