DS7200V2-UK Installer's Guide
Copyright
2007 Bosch Security Systems, Inc.
P/N: 4998152533-02 Page 115
PART IV: CONTROL PANEL PROGRAMMING
Alternate Communication Heartbeat Retries
•
Address: 3539-3540
•
Default: 0, 2
•
Selections: 0 to 99 retries
Use this parameter to define how many times the DX4020 tries to send reports to the ARC before declaring a communication
failure.
This parameter uses two address. Address 3539 sets the 10’s value, and Address 3540 sets the 1’s value. For example, if you
want the DX4020 to make 10 communication attempts before declaring a communication failure, enter “1” in Address 3539
and “0” in Address 3540.
Network Interface Module Options
•
Address: 3541
•
Default: 0
•
Selections: 0-3
Enter This Data Digit to Select Options
Network Interface Module Options
0
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15
No Alternate Communication
•
Enable Alternate Communication
•
•
Include IP Address
•
•
Reserved
Reserved
•
Enable Alternate Communication: Select this option to supervise the connection between the control panel and the
network interface module (DX4020). The network interface module’s DIP switch address must be set to 134. Do not select
this option if there is no network interface module connected to the system.
•
Include IP Address: Select this option to use the IP address entered in IP Address 1 (2) for Destination 1 (2) (see page
112) instead of the IP address stored in the DX4020 for network communication. Select “Enable Alternate Communication” in
Alternate Communication Options
on page 113 for the appropriate IP address. Select this options when using a DX4020. Do
not select this option when using a DX4010i.