PART IV: CONTROL PANEL PROGRAMMING
Format for Destination 1 (2)
•
Address:
−
Reporting Format for Destination 1: 0064
−
Reporting Format for Destination 2: 0130
•
Default: 6 (BSIA Fast Format)
•
Selections:
−
2 = Contact ID
−
3 = SIA 300
−
4 = Basic Pager
−
6 = BSIA Fast Format
−
7 = Personal Dialing Format
−
11 = SIA 300 with Text Blocks
This parameter selects the reporting format. All reports for this destination are sent in the format chosen here.
Leave this parameter at the default setting to transmit reports in BSIA Fast Format.
If you configure the control panel for network communication, you must set this parameter to Contact ID. See Network
Communication
on page 112 for more information. Firmware revision 2.10 or greater is required for network communication.
Check control panel communications (from control panel to ARC) to verify that the control panel is
communicating properly in the selected reporting format at least once a year.
See the following sections for more information on reporting format operation and configuration:
•
Personal Dialing Format Configuration (page 106)
•
BSIA Fast Format Configuration (page 107)
•
Basic Pager Display (page 109)
•
SIA 300 with Text Blocks (page 111)
•
Control Panel Events and Reporting Formats (page 124)