PART IV: CONTROL PANEL PROGRAMMING
Configuring Steady, Pulse and One Shot Mode
•
Steady and Toggle Modes: These modes are not affected by the Time Base and Time Multiplier parameters below.
•
Pulse Modes: The system calculates the On Time (activation) and the Off Time for outputs based on the values in the Base
and Multiplier columns (see Table 34). The duration, or On Time, of an output is determined by selecting one of the four
Base options from Table 34. Calculate the Off Time by multiplying the Base by the Multiplier.
The Time Base of 200 ms in Table 34 and Table 35 is only available for on-board outputs.
Base
On Time
(On Time = Time of Base)
Multiplier
Off Time
(Off Time = Base x Multiplier)
Tolerance
0 0
N/A
Always
Off
N/A
1 (200 ms)
200 ms
01-99
200 ms – 19.8 sec
±200 ms
2 (1 sec)
1 sec
01-99
1 – 99 sec
±1 sec
3 (1 min)
1 min
01-99
1 – 99 min
±1 min
4 (1 hr)
1 hr
01-99
1 – 99 hr
±1 hr
Table 34: Pulse Mode Configuration
•
One Shot Modes: The duration of the On Time of a One Shot output is determined by multiplying the Base by the Multiplier.
Base
Multiplier
On Time
(On Time = Base x Multiplier)
Tolerance
0 N/A
0
N/A
1 (200 ms)
01-99
200 ms – 19.8 sec
±200 ms
2 (1 sec)
01-99
1 sec – 99 sec
±1 sec
3 (1 min)
01-99
1 min – 99 min
±1 min
4 (1 hr)
01-99
1 hr – 99 hr
±1 hr
Table 35: One Shot Mode Configuration