Page 88 P/N: 4998152533-02
Copyright
2007 Bosch Security Systems, Inc.
DS7200V2-UK Installer's Guide
PART IV: CONTROL PANEL PROGRAMMING
Function, Output ##
•
Address: See Table 31
•
Default:
−
PO 1: 1|10: Alarm –Controlled zones, 24-hr zones (Fire and Non-Fire)
−
PO 2: 8|8: Enhanced Siren
−
PO 3: 1|6: Strobe
−
PO 4: 8|5: Unconfirmed Alarm
−
PO 5: 8|4: Confirmed Alarm
−
PO 6: 8|7: Bypass
−
PO 7: 8|9: Alarm Cancel
−
PO 8: 8|10: RF Transmitter Missing
−
PO 9: 8|11: RF Transmitter Low Battery
−
PO 10: 8|12: RF Receiver Jamming
•
Selections: 0|0 to 8|15 (see Table 32)
This parameter assigns each output to a specific function. The function determines when the output activates. The Mode, Time
and Multiplier parameters, in combination with this Function parameter, determine when the output deactivates.
All output functions can be reset using [#][5][4] except Alarm Outputs that follow Function Types 1|8 to 1|12 and 2|11, and
those functions that can be reset by pressing [System Reset].
Digit
1
Digit
2
Function Type
Description
0 0
Disabled
0 1
Armed – All, Perimeter
Only, or Partial On
Output activates when the system is armed All On, Perimeter Only, or Partial On. For Steady or Pulse
modes, the output remains activated until the system is turned off.
0 2
Armed – Perimeter Only
or Partial On
Output activates when the system is armed Perimeter Only, or Partial On. For Steady or Pulse modes,
the output remains activated until the system is turned off, or moved to another armed state.
0 3
Armed
–
All
Output activates when the system is turned All On. For Steady or Pulse modes, the output remains
activated until the system is turned off, or moved to another armed state.
0 4
Auto Arm Pre-Arming
Alert
Output activates at the start of the Auto Arm Alert. For Steady or Pulse modes, the output remains
activated for the duration of the alert. See Auto On Alert Time on page 50.
0 5
Exit Delay or Entry
Delay.
Output activates at the start of Exit Delay or Entry Delay. For Steady or Pulse modes, the output
remains activated until entry or exit delay ends.
0 6
Exit
Delay
Output activates at the start of Exit Delay. For Steady or Pulse modes, the output remains activated
until exit delay ends.
0 7
Exit Delay Finished (until
disarmed)
Output activates at the end of Exit Delay. For Steady or Pulse modes, the output remains activated
until the system is disarmed.
0
8
Bell Test on Close
For systems programmed for closing reports, the output activates when the acknowledgement for the
closing report is received. For systems not sending closing reports, the output activates at the end of
Exit Delay. For Steady or Pulse modes, the output remains activated until the system is disarmed.
0 9
Entry
Delay
Output activates at the start of Entry Delay. For Steady or Pulse modes the output remains activated
until Entry Delay ends.
0
10
Entry Delay + Chime
Output activates at the start of Entry Delay. For Steady or Pulse modes, the output remains activated
until entry delay ends. The output also activates whenever a Chime zone is faulted. The output does
not activate if Chime Tone is turned off.
0 11
Exit Delay, Entry Delay,
Chime
Output activates at the start of Exit Delay or Entry Delay. For Steady or Pulse modes, the output
remains activated until Entry or Exit Delay ends. The output also activates whenever a Chime zone is
faulted. The output does not activate if Chime Tone is turned off.
0
12
Phone Line Fail
Output activates when a Phone Line Fail condition is detected. For Steady or Pulse modes, the output
remains activated until the condition is cleared.
This output works independently of Phone Line
Fault Response Options (see the
DS7200V2 Expert Programming Guide
(P/N: 4998153891)).
0 13
Ack Received (any
report)
Output activates when the acknowledgement for any report is received. For Steady or Pulse modes,
[System Reset] resets. This output type is event-driven. See Mode (Steady, Pulse, One Shot), Output
## on page 92 for more information.
0 14
AC
Fail
Output activates when a AC Fail condition is detected. For Steady or Pulse modes, the output remains
activated until the condition is cleared.
0
15
Low or Missing Battery
Output activates when a panel Low or Missing Battery condition occurs. For Steady or Pulse modes,
the output remains activated until the condition is cleared.
Table 32: Output Function Types