DS7200V2-UK Installer's Guide
Copyright
2007 Bosch Security Systems, Inc.
P/N: 4998152533-02 Page 125
PART V: REFERENCE MATERIALS
Event #
Event as shown in
Panel Log
SIA Report
SIA Report Data Contact ID Report Event Description
Zone Types
Linked to Event
RPS
Event
Group
Status
Reports
17 Cross,Unverified
Unverified
Event Burglary
ri {area} BG {loop} 378 Cross-zone
Trouble
A fault on one non-
fire zone type with the
Cross Zone Option
selected. This is not
an alarm event.
any with Cross
Zone Option
3
18
Alarm Exit Error
Exit Alarm
ri {area} EA {loop} 374 Exit Error
(zone)
Zone faulted at the
end of Exit Delay.
11- Delay 1
12- Delay 2
3
19
Alrm Recent Clse
Recent Closing ri {area} CR {loop} 134 Entry/Exit
Alarm event within 2
minutes of closing.
11- Delay 1
12- Delay 2
3
20
Alrm Recent Clse
Recent Closing ri {area} CR {loop} 130 Burglary
Alarm event within 2
minutes of closing.
10- Keyswitch
13- Follower
14- Instant
3
21
Auto On Extended
Closing Extend ri {area} CE {user} 464 Auto-arm Time
Extended
Auto On Sked
delayed one hour by
user. Report follows
Open/Close routing.
10
22
Battery Low
System Battery
Trouble
YT
302 Low System
Battery
Panel battery is low.
12
R
S
23
Battery Missing
System Battery
Missing
YM 311
Battery
Missing/Dead
Panel battery is
missing. Very low,
shorted, or open
batteries are reported
as missing.
12
R
S
24
Rstrl Batt Low
System Battery
Restoral
YR
302 Low System
Battery
Battery restoral from
low battery.
12
R
S
25
Rstrl Bat Missng
System Battery
Restoral
YR 311
Battery
Missing/Dead
Battery Restoral from
missing battery
12
R
S
26
Bypass,Fire,User
Fire Bypass
ri {area} FB {loop} 571 Fire bypass
Selective bypass by
user, fire zone types
1- Fire
2- Fire with
Alarm
Verification
15
27 Bypass,Fire,
RPS
Fire Bypass
ri {area} FB {loop} 571 Fire bypass
Selective bypass by
RPS, fire zone types.
1- Fire
2- Fire with
Alarm
Verification
28 Bypass,Ctrl,User Burglary
Bypass
ri {area} BB {loop} 570 Zone/Sensor
bypass
Selective bypass by
user, zone types.
10 to 15- Zone
Types
15
29 Bypass,Ctrl,
RPS
Burglary
Bypass
ri {area} BB {loop} 570 Zone/Sensor
bypass
Selective bypass by
RPS, zone types.
10 to 15- Zone
Types
30 Bypass,24hr,User
Burglary
Bypass
ri {area} BB {loop} 572 24-Hr Zone
Bypass
Selective bypass by
user, 24-hour non-fire
zone types.
3 to 9- 24-hour,
Non-Fire Zone
Types
15
31 Bypass,24hr,
RPS
Burglary
Bypass
ri {area} BB {loop} 572 24-Hr Zone
Bypass
Selective bypass by
RPS, 24-hour non-fire
zone types.
3 to 9- 24-hour,
Non-Fire Zone
Types
32 Bypass,Forced
Zn
Burglary
Bypass
ri {area} BB {loop} 570 Zone/Sensor
bypass
Zone force armed at
force arming.
10 to 15- Zone
Types
15
33 Bypass,Swinger Burglary
Bypass
ri {area} BB {loop} 575 Swinger Shunt Zone Swinger
Shunted.
All zone types
15
34
UnBypss,Fire, Usr Fire Bypass
ri {area} FU {loop} 571 Fire bypass
User cleared bypass
(unbypass), Fire zone
types.
1- Fire
2- Fire with
Alarm
Verification
15
35 UnBypss,Ctrl,Usr Burglary
Unbypass
ri {area} BU {loop} 570 Zone/Sensor
bypass
User cleared bypass
(unbypass), zone
types.
10 to 15- Zone
Types
15
36 UnBypss,24hr,Usr
Burglary
Unbypass
ri {area} BU {loop} 572 24-Hr Zone
Bypass
User cleared bypass
(unbypass), 24-hour
zone types.
3 to 9- 24-hour,
Non-Fire Zone
Types
15
Table 47: Control Panel Events and Reporting Formats (continued)