Application macros
93
Torque Control macro
This macro provides parameter settings for applications that require torque control of
the motor. Control can also be switched to speed control using a digital input. To
enable the macro, set the value of parameter
to 8 (TORQUE CTRL).
For the parameter default values, see section
Default values with different macros
. If you use other than the default connections presented below, see
on page
.
Default I/O connections
1…10 kohm
3)
X1A
1
SCR
Signal cable shield (screen)
2
AI1
Motor speed reference (Speed)
: 0…10 V
3
GND
Analog input circuit common
4
+10V
Reference voltage: +10 VDC, max. 10 mA
5
AI2
Motor torque reference (Torque)
: 4…20 mA
4)
6
GND
Analog input circuit common
7
AO
Motor speed value
: 0…20 mA
8
GND
Analog output circuit common
9
+24V
Auxiliary voltage output: +24 VDC, max. 200 mA
10
GND
Auxiliary voltage output common
11
DCOM
Digital input common
12
DI1
Stop (0) / Start (1) (Speed)
13
DI2
Forward (0) / Reverse (1)
1)
14
DI3
Speed (0) / Torque (1) control selection
15
DI4
Constant speed 1
16
DI5
Acceleration and deceleration selection
2)
X1B
17
ROCOM
Relay output
No fault [Fault (-1)]
18
RONC
19
RONO
20
DOSRC
Digital output, max. 100 mA
No fault [Fault (-1)]
21
DOOUT
22
DOGND
max. 500 ohm
1)
Speed control: Changes rotation direction.
Torque control: Changes torque direction.
2)
0 = ramp times according to parameters
.
1 = ramp times according to parameters
.
3)
360 degree grounding under a clamp.
4)
The signal source must be powered externally.
See the manufacturer’s instructions. An
example of a connection using a two-wire
sensor is given on page
Tightening torque = 0.5 N·m / 4.4 lbf. in.
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......