Start-up, control with I/O and ID Run
47
MANUAL ENTRY OF START-UP DATA (parameter group 99)
If you have an Assistant Control Panel, select the language
(the Basic Control Panel does not support languages). See
parameter
for the values of the available language
alternatives.
The general parameter setting procedure is described below for the Basic
Control Panel. You find more detailed instructions for the Basic Control Panel
on page
. Instructions for the Assistant Control Panel are on page
The general parameter setting procedure:
1. To go to the Main menu, press
if the bottom line shows OUTPUT;
otherwise press
repeatedly until you see MENU at the bottom.
2. Press
keys /
until you see “PAr” and press
.
3. Find the appropriate parameter group with
keys /
and press
.
4. Find the appropriate parameter in the group with
keys /
.
5. Press and hold
for about two seconds until the parameter value is
shown with
under the value.
6. Change the value with keys
/
. The value changes faster while
you keep the key pressed down.
7. Save the parameter value by pressing
.
Select the application macro (parameter
). The general
parameter setting procedure is given above.
The default value 1 (ABB STANDARD) is suitable in most cases.
Select the motor control mode (parameter
).
1 (VECTOR:SPEED) is suitable in most cases. 2 (VECTOR:TORQ) is
suitable for torque control applications. 3 (SCALAR:FREQ) is recommended
• for multimotor drives when the number of the motors connected to the
drive is variable
• when the nominal current of the motor is less than 20% of the nominal
current of the drive
• when the drive is used for test purposes with no motor connected.
9901 LANGUAGE
PAR EDIT
ENGLISH
CANCEL
SAVE
00:00
[0]
REM
REM
MENU FWD
rEF
REM
PAR FWD
-01-
REM
PAR FWD
2001
REM
PAR FWD
2002
SET
REM
rpm
PAR
SET
FWD
1500
REM
rpm
PAR
SET
FWD
1600
REM
PAR FWD
2002
REM
PAR FWD
9902
REM
PAR FWD
9904
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......