Start-up, control with I/O and ID Run
48
Enter the motor data from the motor nameplate:
Note
:
Set the motor data to
exactly the same value as on
the motor nameplate. For
example, if the motor nominal
speed is 1440 rpm on the
nameplate, setting the value of
parameter
MOTOR NOM
SPEED to 1500 rpm results in
the wrong operation of the drive.
• motor nominal voltage (parameter
)
• motor nominal current (parameter
)
Allowed range: 0.2…2.0 ·
I
2N
A
• motor nominal frequency (parameter
• motor nominal speed (parameter
• motor nominal power (parameter
Select the motor identification method (parameter
The default value 0 (OFF/IDMAGN) using the identification magnetization is suitable for
most applications. It is applied in this basic start-up procedure. Note however that this
requires that:
• parameter
is set to 1 (VECTOR: SPEED) or 2 (VECTOR: TORQ)
is set to 3 (SCALAR: FREQ), and parameter
is set to 3 (SCALAR
FLYSTART) or 5 (FLY + BOOST).
If your selection is 0 (OFF/IDMAGN), move to the next step.
Value 1 (ON) should be selected if:
- the operation point is near zero speed, and/or
- operation at torque range above the motor nominal torque over a wide speed range and
without any measured speed feedback is required.
If you decide to do the ID Run (value 1 (ON)), continue by following the separate instructions
given on page
in section
and then return to step
on page
.
M2AA 200 MLA 4
1475
1475
1470
1470
1475
1770
32.5
56
34
59
54
59
0.83
0.83
0.83
0.83
0.83
0.83
3GAA 202 001 - ADA
180
IEC 34-1
6210/C3
6312/C3
Cat. no
35
30
30
30
30
30
50
50
50
50
50
60
690 Y
400 D
660 Y
380 D
415 D
440 D
V
Hz
kW
r/min
A
cos
IA/IN t E/s
Ins.cl. F
IP 55
No
IEC 200 M/L 55
3
motor
ABB Motors
380 V
supply
voltage
REM
PAR FWD
9905
REM
PAR FWD
9906
REM
PAR FWD
9907
REM
PAR FWD
9908
REM
PAR FWD
9909
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......