Actual signals and parameters
183
21 START/STOP
Start and stop modes of the motor
2101
START FUNCTION
Selects the motor starting method.
AUTO
AUTO
The drive starts the motor instantly from zero frequency if parameter
MOTOR CTRL MODE setting is SCALAR:FREQ. If flying start is required use
selection SCAN START.
If parameter
MOTOR CTRL MODE value is VECTOR:SPEED/
VECTOR:TORQ, the drive pre-magnetises the motor with DC current before
the start. The pre-magnetising time is defined by parameter
DC MAGN
TIME. See selection DC MAGN.
1
DC MAGN
The drive pre-magnetises the motor with DC current before the start. The
pre-magnetising time is defined by parameter
DC MAGN TIME.
MOTOR CTRL MODE value is VECTOR:SPEED/
VECTOR:TORQ, DC magnetising guarantees the highest possible
break-away torque when the pre-magnetising is set long enough.
Note:
Starting to a rotating machine is not possible when DC MAGN is
selected.
WARNING!
The drive will start after the set pre-magnetising time has passed
even if the motor magnetisation is not completed. Ensure always in
applications where a full break-away torque is essential, that the constant
magnetising time is long enough to allow generation of full magnetisation and
torque.
2
TORQ BOOST
Torque boost should be selected if a high break-away torque is required.
Used only when parameter
MOTOR CTRL MODE setting is
SCALAR:FREQ.
The drive pre-magnetises the motor with DC current before the start. The
pre-magnetising time is defined by parameter
DC MAGN TIME.
Torque boost is applied at start. Torque boost is stopped when output
frequency exceeds 20 Hz or when it is equal to the reference value. See
parameter
TORQ BOOST CURR.
Note:
Starting to a rotating machine is not possible when TORQ BOOST is
selected.
WARNING!
The drive will start after the set pre-magnetising time has passed
although the motor magnetisation is not completed. Ensure always in
applications where a full break-away torque is essential, that the constant
magnetising time is long enough to allow generation of full magnetisation and
torque.
4
SCAN START
Frequency scanning flying start (starting to a rotating machine). Based on
frequency scanning (interval
MAXIMUM FREQ...
MINIMUM
FREQ) to identify the frequency. If frequency identification fails, DC
magnetisation is used (see selection DC MAGN).
6
SCAN + BOOST
Combines scanning start (starting to a rotating machine) and torque boost.
See selections SCANSTART and TORQ BOOST. If frequency identification
fails, torque boost is used.
Used only when parameter
MOTOR CTRL MODE setting is
SCALAR:FREQ.
7
2102
STOP FUNCTION
Selects the motor stop function.
COAST
COAST
Stop by cutting off the motor power supply. The motor coasts to a stop.
1
RAMP
Stop along a ramp. See parameter group
.
2
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......