Program features
117
Underload Protection
Loss of motor load may indicate a process malfunction. The drive provides an
underload function to protect the machinery and process in such a serious fault
condition. Supervision limits - underload curve and underload time - can be chosen
as well as the action taken by the drive upon the underload condition (alarm
indication / fault indication & drive stop / no reaction).
Settings
Parameters
Earth Fault Protection
The Earth Fault Protection detects earth faults in the motor or motor cable. The
protection is active only during start.
An earth fault in the input power line does not activate the protection.
Settings
Parameter
EARTH FAULT
Incorrect wiring
Defines the operation when incorrect input power cable connection is detected.
Settings
Parameter
WIRING FAULT
Input phase loss
Input phase loss protection circuits supervise the input power cable connection
status by detecting intermediate circuit ripple. If a phase is lost, the ripple increases.
Settings
Parameter
SUPPLY PHASE
Preprogrammed faults
Overcurrent
The overcurrent trip limit for the drive is 325% of the drive nominal current.
DC overvoltage
The DC overvoltage trip limit is 420 V (for 200 V drives) and 840 V (for 400 V drives).
DC undervoltage
The DC undervoltage trip limit is 162 V (for 200 V drives) and 308 V (for 400 V
drives).
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......