Actual signals and parameters
195
2613
USER DEFINED F2
Defines the second frequency point of the custom U/f curve.
20
0.0...500.0 Hz
Frequency
1 = 0.1 Hz
2614
USER DEFINED U3
Defines the third voltage point of the custom U/f curve at the frequency
defined by parameter
USER DEFINED F3. See section
47.5% of
U
N
0...120% of
U
N
V
Voltage
1 = 1 V
2615
USER DEFINED F3
Defines the third frequency point of the custom U/f curve.
25
0.0...500.0 Hz
Frequency
1 = 0.1 Hz
2616
USER DEFINED U4
Defines the fourth voltage point of the custom U/f curve at the frequency
defined by parameter
USER DEFINED F4. See section
76% of
U
N
0...120% of
U
N
V
Voltage
1 = 1 V
2617
USER DEFINED F4
Defines the fourth frequency point of the custom U/f curve.
40
0.0...500.0 Hz
Frequency
1 = 0.1 Hz
2618
FW VOLTAGE
Defines the voltage of the U/f curve when frequency is equal to or exceeds
the motor nominal frequency (
MOTOR NOM FREQ). See section
95% of
U
N
0...120% of
U
N
V
Voltage
1 = 1 V
29 MAINTENANCE
TRIG
Maintenance triggers
2901
COOLING FAN TRIG
Defines the trigger point for the drive cooling fan run time counter. Value is
compared to parameter
COOLING FAN ACT value.
0
0.0...6553.5 kh
Time. If parameter value is set to zero, the trigger is disabled.
1 = 0.1 kh
2902
COOLING FAN ACT
Defines the actual value for the cooling fan run time counter. When
parameter
COOLING FAN TRIG has been set to a non zero value, the
counter starts. When the actual value of the counter exceeds the value
defined by parameter
, a maintenance notice is displayed on the panel.
0
0.0...6553.5 kh
Time. Parameter is reset by setting it to zero.
1 = 0.1 kh
2903
REVOLUTION TRIG
Defines the trigger point for the motor revolution counter. Value is compared
to parameter
REVOLUTION ACT value.
0
0...65535 Mrev
Millions of revolutions. If parameter value is set to zero, the trigger is
disabled.
1 = 1 Mrev
2904
REVOLUTION ACT
Defines the actual value for the motor revolution counter. When parameter
REVOLUTION TRIG has been set to a non zero value, the counter
starts. When the actual value of the counter exceeds the value defined by
parameter
, a maintenance notice is displayed on the panel.
0
0...65535 Mrev
Millions of revolutions. Parameter is reset by setting it to zero.
1 = 1 Mrev
2905
RUN TIME TRIG
Defines the trigger point for the drive run time counter. Value is compared to
parameter
0
0.0...6553.5 kh
Time. If parameter value is set to zero, the trigger is disabled.
1 = 0.1 kh
2906
RUN TIME ACT
Defines the actual value for the drive run time counter. When parameter
RUN TIME TRIG has been set to a non zero value, the counter starts. When
the actual value of the counter exceeds the value defined by parameter
,
a maintenance notice is displayed on the panel.
0
0.0...6553.5 kh
Time. Parameter is reset by setting it to zero.
1 = 0.1 kh
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......