Application macros
94
User macros
In addition to the standard application macros, it is possible to create three user
macros. The user macro allows the user to save the parameter settings, including
group
, and the results of the motor identification into the
permanent memory and recall the data at a later time. The panel reference is also
saved if the macro is saved and loaded in local control. The remote control setting is
saved into the user macro, but the local control setting is not.
The steps below show how to create and recall User macro 1. The procedure for the
other two user macros is identical, only the parameter
values are different.
To create User macro 1:
• Adjust the parameters. Perform the motor identification if it is needed in the
application but it is not done yet.
• Save the parameter settings and the results of the motor identification to the
permanent memory by changing parameter
• Press
(Assistant Control Panel) or
(Basic Control Panel).
To recall User macro 1:
to 0 (USER S1 LOAD).
• Press
(Assistant Control Panel) or
(Basic Control Panel) to load.
The user macro can also be switched through digital inputs (see parameter
Note:
User macro load restores the parameter settings including group
and the results of the motor identification. Check that the settings
correspond to the motor used.
Hint:
The user can for example switch the drive between three motors without
having to adjust the motor parameters and to repeat the motor identification every
time the motor is changed. The user needs only to adjust the settings and perform
the motor identification once for each motor and then to save the data as three user
macros. When the motor is changed, only the corresponding user macro needs to
be loaded, and the drive is ready to operate.
SAVE
ENTER
MENU
SAVE
ENTER
MENU
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......