Actual signals and parameters
148
Parameters – short form list
Parameters – short form list
Index
Name/Selection
Description
Def
Custom
10
START/STOP/DIR
The sources for external start, stop and direction control
1001
EXT1 COMMANDS
Defines the connections and the source for the start, stop and
direction commands for external control location 1 (EXT1).
DI1,2
1002
EXT2 COMMANDS
Defines the connections and the source for the start, stop and
direction commands for external control location 2 (EXT2).
NOT SEL
1003
DIRECTION
Enables the control of rotation direction of the motor, or fixes the
direction.
REQUEST
1010
JOGGING SEL
Defines the signal that activates the jogging function.
NOT SEL
11
REFERENCE SELECT Panel reference type, external control location selection and
external reference sources and limits
1101
KEYPAD REF SEL
Selects the type of the reference in local control mode.
REF1
1102
EXT1/EXT2 SEL
Defines the source from which the drive reads the signal that
selects between the two external control locations, EXT1 or
EXT2.
EXT1
1103
REF1 SELECT
Selects the signal source for external reference REF1.
AI1
1104
REF1 MIN
Defines the minimum value for external reference REF1.
0
1105
REF1 MAX
Defines the maximum value for external reference REF1.
Eur: 50 / US: 60
1106
REF2 SELECT
Selects the signal source for external reference REF2.
AI2
1107
REF2 MIN
Defines the minimum value for external reference REF2.
0
1108
REF2 MAX
Defines the maximum value for external reference REF2.
100
12
CONSTANT SPEEDS
Constant speed selection and values.
1201
CONST SPEED SEL
Activates the constant speeds or selects the activation signal.
DI3,4
1202
CONST SPEED 1
Defines constant speed (or drive output frequency) 1.
Eur: 5 / US: 6
1203
CONST SPEED 2
Defines constant speed (or drive output frequency) 2.
Eur: 10 / US: 12
1204
CONST SPEED 3
Defines constant speed (or drive output frequency) 3.
Eur: 15 / US: 18
1205
CONST SPEED 4
Defines constant speed (or drive output frequency) 4.
Eur: 20 / US: 24
1206
CONST SPEED 5
Defines constant speed (or drive output frequency) 5.
Eur: 25 / US: 30
1207
CONST SPEED 6
Defines constant speed (or drive output frequency) 6.
Eur: 40 / US: 48
1208
CONST SPEED 7
Defines constant speed (or drive output frequency) 7.
Eur: 50 / US: 60
1209
TIMED MODE SEL
Selects timed function activated speed into use when parameter
1201 CONST SPEED SEL selection is TIMED FUN1&2.
CS1/2/3/4
13
ANALOGUE INPUTS
Analog input signal processing
1301
MINIMUM AI1
Defines the minimum %-value that corresponds to minimum mA/
(V) signal for analog input AI1.
0,01
1302
MAXIMUM AI1
Defines the maximum %-value that corresponds to maximum
mA/(V) signal for analog input AI1.
100
1303
FILTER AI1
Defines the filter time constant for analog input AI1, i.e the time
within 63% of a step change is reached.
0.1
1304
MINIMUM AI2
Defines the minimum %-value that corresponds to minimum mA/
(V) signal for analog input AI2.
0,01
1305
MAXIMUM AI2
Defines the maximum %-value that corresponds to maximum
mA/(V) signal for analog input AI2.
100
1306
FILTER AI2
Defines the filter time constant for analog input AI2.
0.1
14
RELAY OUTPUTS
Status information indicated through relay output, and relay
operating delays
1401
RELAY OUTPUT 1
Selects a drive status indicated through relay output RO.
FAULT(-1)
1404
RO 1 ON DELAY
Defines the operation delay for relay output RO.
0
1405
RO 1 OFF DELAY
Defines the release delay for relay output RO.
0
15
ANALOGUE OUTPUTS Selection of the actual signals to be indicated through analog
output and output signal processing
1501
AO1 CONTENT SEL
Connects a drive signal to analog output AO.
103
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......