Actual signals and parameters
152
3002
PANEL COMM ERR
Selects how the drive reacts to a control panel communication
break.
FAULT
3003
EXTERNAL FAULT 1
Selects an interface for an external fault 1 signal.
NOT SEL
3004
EXTERNAL FAULT 2
Selects an interface for an external fault 2 signal.
NOT SEL
3005
MOT THERM PROT
Selects how the drive reacts when the motor overtemperature is
detected.
FAULT
3006
MOT THERM TIME
Defines the thermal time constant for the motor thermal model.
500
3007
MOT LOAD CURVE
Defines the load curve together with parameters 3008 ZERO
SPEED LOAD and 3009 BREAK POINT FREQ.
100
3008
ZERO SPEED LOAD
Defines the load curve together with parameters 3007 MOT
LOAD CURVE and 3009 BREAK POINT FREQ.
70
3009
BREAK POINT FREQ
Defines the load curve together with parameters 3007 MOT
LOAD CURVE and 3008 ZERO SPEED LOAD.
35
3010
STALL FUNCTION
Selects how the drive reacts to a motor stall condition.
NOT SEL
3011
STALL FREQUENCY
Defines the frequency limit for the stall function.
20
3012
STALL TIME
Defines the time for the stall function.
20
3013
UNDERLOAD FUNC
Selects how the drive reacts to underload.
NOT SEL
3014
UNDERLOAD TIME
Defines the time limit for the underload function.
20
3015
UNDERLOAD CURVE Selects the load curve for the underload function.
1
3016
SUPPLY PHASE
Selects how the drive reacts to supply phase loss, i.e. when DC
voltage ripple is excessive.
FAULT
3017
EARTH FAULT
Selects how the drive reacts when an earth (ground) fault is
detected in the motor or the motor cable.
ENABLE
3018
COMM FAULT FUNC
Selects how the drive reacts in a fieldbus communication break.
NOT SEL
3019
COMM FAULT TIME
Defines the time delay for the fieldbus communication break
supervision.
3
3021
AI1 FAULT LIMIT
Defines a fault level for analog input AI1.
MINIMUM AI1.
3022
AI2 FAULT LIMIT
Defines a fault level for analog input AI2.
MINIMUM AI2.
3023
WIRING FAULT
Selects how the drive reacts when incorrect input power and
motor cable connection is detected.
ENABLE
31
AUTOMATIC RESET
Automatic fault reset.
3101
NR OF TRIALS
Defines the number of automatic fault resets the drive performs
within the time defined by parameter 3102 TRIAL TIME.
0
3102
TRIAL TIME
Defines the time for the automatic fault reset function.
30
3103
DELAY TIME
Defines the time that the drive will wait after a fault before
attempting an automatic reset.
0
3104
AR OVERCURRENT
Activates/deactivates the automatic reset for the overcurrent
fault.
DISABLE
3105
AR OVERVOLTAGE
Activates/deactivates the automatic reset for the intermediate
link overvoltage fault.
DISABLE
3106
AR UNDERVOLTAGE
Activates/deactivates the automatic reset for the intermediate
link undervoltage fault.
DISABLE
3107
AR AI<MIN
Activates/deactivates the automatic reset for fault AI<MIN.
DISABLE
3108
AR EXTERNAL FLT
Activates/deactivates the automatic reset for the EXTERNAL
FAULT 1/2.
DISABLE
32
SUPERVISION
Signal supervision. Supervision status can be monitored with
relay or transistor output.
3201
SUPERV 1 PARAM
Selects the first supervised signal.
103
3202
SUPERV 1 LIM LO
Defines the low limit for the first supervised signal selected by
parameter 3201 SUPERV 1 PARAM.
-
3203
SUPERV 1 LIM HI
Defines the high limit for the first supervised signal selected by
parameter 3201 SUPERV 1 PARAM.
-
3204
SUPERV 2 PARAM
Selects the second supervised signal.
104
3205
SUPERV 2 LIM LO
Defines the low limit for the second supervised signal selected
by parameter 3204 SUPERV 2 PARAM.
-
Parameters – short form list
Index
Name/Selection
Description
Def
Custom
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......