Fault tracing
282
1000
PAR HZRPM
(6320)
bit 15
Incorrect speed/frequency limit
parameter setting
Check parameter settings. Check that following
applies:
,
,
are within range.
1003
PAR AI SCALE
(6320)
bit 15
Incorrect analog input AI signal
scaling
Check parameter group
settings. Check that following applies:
1004
PAR AO SCALE
(6320)
bit 15
Incorrect analog output AO
signal scaling
Check parameter group
settings. Check that following applies:
.
1005
PAR PCU 2
(6320)
bit 15
Incorrect motor nominal power
setting
Check parameter
setting. Following must apply:
1.1 < (
MOTOR
NOM VOLT · 1.73 /
P
N
) < 3.0
Where
P
N
= 1000 ·
MOTOR NOM POWER (if
units are in kW)
or
P
N
= 746 ·
MOTOR NOM POWER (if units
are in HP).
1007
PAR FBUSMISS
(6320)
bit 15
Fieldbus control has not been
activated.
Check fieldbus parameter settings. See chapter
Fieldbus control with fieldbus adapter
1009
PAR PCU 1
(6320)
bit 15
Incorrect motor nominal speed/
frequency setting
Check parameter settings. Following must apply:
1 < (60 ·
MOTOR NOM FREQ /
MOTOR
NOM SPEED) < 16
0.8 <
MOTOR NOM SPEED / (120 ·
MOTOR NOM FREQ / Motor poles) < 0.992
1015
PAR CUSTOM U/F
(6320)
bit 15
Incorrect voltage to frequency
(U/f) ratio voltage setting.
...
settings.
1017
PAR SETUP 1
(6320)
bit 15
It is not allowed to use MTAC
encoder module, frequency
input signal and frequency
output signal simultaneously.
Disable frequency output, frequency input or
encoder:
- change transistor output to digital mode (value of
parameter
- change frequency input selection to other value in
parameter groups
40 PROCESS PID SET 1, 41 PROCESS PID SET 2
and
, or
- disable (parameter
) and remove MTAC
encoder module.
CODE
FAULT
CAUSE
WHAT TO DO
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......